ECU-P1761

4-ch Isolated Digital Input, 4-ch Isolated Relay Output with IRIG-B Board
  • CE/FCC Certification
  • 4 x Isolated Digital Input
  • 4 x Isolated Relay Output
  • 1 x IRIG-B
  • PCI Extension
  • OperationTemp: -25~ 70°C
The ECU-P1761 is a PCI extension card with Digital Input and Relay Output function to fulfill the acquisition requirement in power automation. With 4x DI, 4x RO and 1x IRIG-B,
ECU-P1761 enrich the Advantech acquisition solution under power & energy x86 architecture UNO-4673A/4683 and ECU-4784 computers.

Product Specifications Download Spec

  • Part Number
  • Details
Digital Input
  • Channels
  • Connector
  • Input Type
  • Input Voltage
  • Isolation Voltage
  • Response time
Environment
  • Humidity (Operating)
  • Humidity (Storage)
  • Temperature (Operating)
General
  • Bus Interface
  • Certification
  • Connector
  • Dimensions
  • Power Requirements
IRIG-B
  • IRIG Interface
  • Precision
  • Resolution of time
Relay Output
  • Channels
  • Connector
  • Isolation Voltage
  • Max. Switching Voltage
  • Operate/ Release Time
  • Output Type
  • Relay Output Current
  • Relay Output Voltage

Digital Input

  • Channels

    ECU-P1761A-AE 4
  • Connector

    ECU-P1761A-AE Terminal Block
  • Input Type

    ECU-P1761A-AE Wet Contact (Sink)
  • Input Voltage

    ECU-P1761A-AE Logic 0: 0~10 V Logic 1: 30~48 V
  • Isolation Voltage

    ECU-P1761A-AE 2,500 VDC
  • Response time

    ECU-P1761A-AE 1ms

Environment

  • Humidity (Operating)

    ECU-P1761A-AE 5 ~ 95 % RH, non-condensing
  • Humidity (Storage)

    ECU-P1761A-AE 5 ~ 95% RH, non-condensing
  • Temperature (Operating)

    ECU-P1761A-AE -25~ 70°C (-13 ~ 158°F) IEC 60068-2-2 with 100% CPU/ I/O loading, 24 hrs

General

  • Bus Interface

    ECU-P1761A-AE PCI
  • Certification

    ECU-P1761A-AE CE, FCC, IEC-61850-3 Compliant
  • Connector

    ECU-P1761A-AE 120-pin connector for UNO- 4673A/4683/ECU-4784
  • Dimensions

    ECU-P1761A-AE 5.3" x 6.0" (136 x 150 mm)
  • Power Requirements

    ECU-P1761A-AE 5 V @ 150 mA (typical) 3.3 V @ 60 mA (typical

IRIG-B

  • IRIG Interface

    ECU-P1761A-AE BNC
  • Precision

    ECU-P1761A-AE 1ms
  • Resolution of time

    ECU-P1761A-AE 1s

Relay Output

  • Channels

    ECU-P1761A-AE 4
  • Connector

    ECU-P1761A-AE Terminal Block
  • Isolation Voltage

    ECU-P1761A-AE 2500 VDC
  • Max. Switching Voltage

    ECU-P1761A-AE 400VAC
  • Operate/ Release Time

    ECU-P1761A-AE Max. 8 ms
  • Output Type

    ECU-P1761A-AE Relay: 1 Form C
  • Relay Output Current

    ECU-P1761A-AE 25°C 3A, 70°C 1A
  • Relay Output Voltage

    ECU-P1761A-AE 250 VAC /VDC